Untested materials: UK21/F012

Adopted EU recommendation FIRE-050. UK approved recommendation on the substituting approved materials with untested materials.

Question

Is it acceptable to replace trademark-tested non-combustible insulation material with a similar non-combustible insulation material without testing?

Recommendation

Replacement of non-combustible insulation material in A/B class divisions, HSC divisions and fire doors without testing of the whole construction is not acceptable considering Annex 1, Part 3, Chapter 3.5.1 of the International Code for Application of Fire Test Procedures, 2010 (Res. MSC.307(88)), i.e. 鈥淭he material used in the test shall not be replaced by any other materials that have not been tested in accordance with this Code and/or accepted by the Administration鈥�.

References

  • International Code for Application of Fire Test Procedures, 2010
  • MSN 1874 as amended
  • as amended

Items affected

  • UK/3.11, 鈥淎鈥� and 鈥淏鈥� Class divisions fire integrity: 鈥淎鈥� class divisions.
  • UK/3.16, Fire Doors
  • UK/3.34, Fire resisting divisions for high speed craft
  • UK/3.35, Fire doors on high speed craft