A and B class divisions fire standard curve: UK21/F006
Adopted EU recommendation FIRE-018. UK approved recommendation on the use of fire test results for UK type approval.
Question
Can the results of a fire test be performed following the hydrocarbon time/ temperature curve indicated in EN 1363-2, in lieu of the time/temperature curve in ISO 834/ EN 1363-1, be accepted for issuance of UK type examination (Module B) certification?
Recommendation
The reply to this question is 鈥渘o鈥�. Fire tests are to be performed following the requirements and procedures set out in the Fire Test Procedures Code.鈥�
References
- Fire Test Procedures Code
- MSN 1874 as amended
- The Merchant Shipping (Marine Equipment) Regulations 2016 as amended
Items affected
- UK/3.11, A鈥� & 鈥楤鈥� Class divisions fire integrity